top of page

Excess Temperature Thermocouple

Flynn Part Number: 173124

173124.jpg

8.16* Excess Temperature Limit Interlock.

​

8.16.1 An excess temperature limit interlock shall be provided and interlocked into the burner management system, unless permitted by 8.16.2.

​

8.16.3 Operation of the excess temperature limit interlock shall cut off the heating system before the oven's maximum temperature, as specified by the oven manufacturer, is exceeded.

​

8.16.4 Operation of the excess temperature limit interlock shall require manual reset before restart of the furnace or affected furnace zone.

​

8.16.5 Open-circuit failure of the temperature-sensing components of the excess temperature limit interlock shall cause the same response as an excess temperature condition.

​

8.16.6* Excess temperature limit interlocks shall be equipped with temperature indication.

​

8.16.7* The temperature-sensing element of the excess temperature limit interlock shall be selected for the temperature and atmosphere to which they are exposed.

​

8.16.8* The temperature-sensing element of the excess temperature limit interlock shall be located where recommended by the oven manufacturer or designer.

​

8.16.9* The excess temperature limit interlock shall indicate its set point in temperature units that are consistent with the primary temperature-indicating controller.

bottom of page